首页> 外文期刊>IEEE Transactions on Dielectrics and Electrical Insulation >Investigation of vibration impacts on HVAC transformer from HVDC system under monopole operation
【24h】

Investigation of vibration impacts on HVAC transformer from HVDC system under monopole operation

机译:单极运行下HVDC系统对HVAC变压器的振动影响研究

获取原文
获取原文并翻译 | 示例

摘要

When the high voltage direct current (HVDC) system operates in monopole ground-return mode, DC current flows through the neutral of AC power transformer with the neutral grounded which exacerbates the vibration of the transformer. During the field test of Yibin-Jinhua HVDC system in China, the vibration detection system is deployed to detect the vibration signal of the 500 kV transformer in Luzhou substation, which is close to the grounding substation. The spectrum of the transformer vibration signal is analyzed by means of the wavelet transform, through which the vibration acoustic fingerprint and three typical characteristic parameters, i.e., the distribution percentage of spectral energy, the energy ratio of odd and even harmonics, and the waveform distortion ratio, are extracted respectively. When the HVDC system current increases from 0 A to 5 kA, the impact of DC bias on the operation condition of the 500 kV transformer is investigated through the analysis of the variation of vibration acoustic fingerprint and three characteristic parameters. It is indicated that the energy radio of odd and even harmonics of the 500 kV transformer vibration signal decreases significantly with the increase of the current. In addition, the distribution percentage of spectral energy and the vibration acoustic fingerprint change significantly. This paper demonstrates that the effect of DC bias on the operating condition of the transformer can be accurately assessed by the proposed indices.
机译:当高压直流(HVDC)系统以单极接地模式运行时,直流电流流经交流电源变压器的中性点,而中性点接地则加剧了变压器的振动。在中国宜宾-金华高压直流输电系统的现场测试中,部署了振动检测系统,以检测Lu州变电站中靠近接地变电站的500 kV变压器的振动信号。利用小波变换对变压器振动信号的频谱进行分析,通过小波变换分析振动声指纹和三个典型特征参数,即频谱能量的分布百分比,奇次谐波能量比,波形失真。分别提取。当HVDC系统电流从0 A增加到5 kA时,通过分析振动声指纹的变化和三个特征参数,研究了直流偏置对500 kV变压器运行条件的影响。结果表明,随着电流的增加,500 kV变压器振动信号的奇次谐波和偶次谐波的能量射电大大降低。另外,频谱能量的分布百分比和振动声指纹显着变化。本文表明,可以通过提出的指标准确评估直流偏置对变压器工作条件的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号