首页> 外文期刊>E3S Web of Conferences >Experimental Study on Electrochemical Softening for Cooling Circulating Water in Converter Station
【24h】

Experimental Study on Electrochemical Softening for Cooling Circulating Water in Converter Station

机译:换器站冷却循环水的电化学软化试验研究

获取原文
       

摘要

In this study, the electrochemical softening method was used to treat the simulated drainage of the converter station, and the treatment effect under different water inlet conditions was investigated. The results show that the hardness removal rate is from 10% to 80% when the residence time is from 0.5h to 4h, and the longer the residence time is, the higher the removal rate is. The maximum scale removal capacity reached 2.67g/h/m~(2)when residence time was 1h. Through the formula fitting of several groups of tests, it is concluded that the removal effect can be expressed by the formula C0/C=0.9627e~((17.73at/V))under different water intake (residence time).
机译:在该研究中,使用电化学软化方法来处理转换器站的模拟排水,并研究了不同进水条件下的处理效果。 结果表明,当停留时间为0.5h至4h时,硬度去除率为10%至80%,停留时间越长,去除率越高。 当停留时间为1H时,最大刻度去除容量达到2.67g / h / m〜(2)。 通过几组试验的配方拟合,得出结论,去除效果可以在不同的水摄入(停留时间)下的式CO / C = 0.9627e〜((17.73AT / v))表示。