首页> 外文期刊>E3S Web of Conferences >Influence of Inverter Controller Parameters on the Small-signal Stability of LCC-HVDC System Based on a Practical Project
【24h】

Influence of Inverter Controller Parameters on the Small-signal Stability of LCC-HVDC System Based on a Practical Project

机译:基于实际项目的LCC-HVDC系统小信号稳定性对逆变器控制器参数的影响

获取原文
   

获取外文期刊封面封底 >>

       

摘要

Unreasonable control parameters of the Line Commutated Converter based High Voltage Direct Current (LCC-HVDC) system may induce small-signal instability. This paper studies the impact of inverter controller parameters on steady response of the LCC-HVDC system under weak AC grid condition. Firstly, according to a practical project, the small-signal model of LCC-HVDC system is established based on the switching function. Then, the eigen-analysis method is adopted to study the impact of the controller parameters on the inverter side on the oscillation mode and damping characteristics of the LCC system, and the correctness of results is verified by PSCAD/EMTDC simulation. The conclusion shows that reasonable controller parameters can improve the stability margin of the system.
机译:基于线路换向转换器的高压直流(LCC-HVDC)系统的不合理控制参数可以引起小信号不稳定性。 本文研究了逆变器控制器参数对弱交流电网条件下LCC-HVDC系统稳态响应的影响。 首先,根据一个实际项目,基于切换功能建立LCC-HVDC系统的小信号模型。 然后,采用特征分析方法研究控制器参数对逆变器侧的影响,对LCC系统的振荡模式和阻尼特性,并通过PSCAD / EMTDC仿真验证了结果的正确性。 结论表明,合理的控制器参数可以提高系统的稳定性边缘。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号