首页> 外文期刊>E3S Web of Conferences >The inspection and strength checking of old circular prestressed reinforced concrete pole
【24h】

The inspection and strength checking of old circular prestressed reinforced concrete pole

机译:旧圆形预应力钢筋混凝土杆的检验与实力检查

获取原文
获取外文期刊封面目录资料

摘要

The capacity expansion of the old transmission lines will lead to an increase in the load level of exsiting prestressed reinforced concrete pole. In this work, the structural parameters of old pole were detected by X-ray imaging technology. The force conditions of the modified concrete pole under the design conditions and actual service conditions were analyzed by Midas/civil. And combined with the calculation of bearing capacity of the circular prestressed reinforced concrete section, the strength checking was conducted. The results showed that X-ray imaging technology can be used to detect the number of steel bars in pole. In addition, the reforming scheme that existing prestressed reinforced concrete poles were used and original LGJ70/10 conductors were replaced with LGJ95/15, still possess considerable safety factor under the actual maximum load conditions.
机译:旧传输线的容量膨胀将导致出口预应力钢筋混凝土杆的负荷水平增加。 在这项工作中,X射线成像技术检测了旧极的结构参数。 MIDAS /民间分析了设计条件和实际服务条件下改进的混凝土杆的力条件。 并结合圆形预应力钢筋混凝土截面承载力的计算,进行了强度检查。 结果表明,X射线成像技术可用于检测杆中钢筋的数量。 此外,使用现有预应力钢筋混凝土磁极和原始LGJ70 / 10导体的重整方案被LGJ95 / 15代替,在实际最大载荷条件下仍然具有相当大的安全系数。