首页> 外文期刊>Journal of Electrical Engineering >De-noising of partial discharge signal using wavelet transform for GIS under HVDC
【24h】

De-noising of partial discharge signal using wavelet transform for GIS under HVDC

机译:在HVDC下使用小波变换的小波变换的局部放电信号的去噪

获取原文
获取外文期刊封面目录资料

摘要

Detection and analysis of partial discharge (PD) have been regard as the most effective method for condition monitoring and asset management of gas-insulated structures (GIS) in the power system. However, PD detection sensitivity and accuracy are greatly influenced by on-site noise and interference, resulting in failures in PD severity assessment, defect identification or localization. Although de-noising of PD signal under AC was well studied, related investigations under DC have not been carried out. With the rapid development of HVDC technology, it is a new challenge to eliminate noise from PD signal under DC for diagnosis of related power facilities. Therefore, this paper dealt with the discrimination of PD signal based on wavelet transform (WT) techniques for HVDC GIS, aiming to improve the sensitivity and accuracy of insulation diagnosis. Experimental setup was configured to generate PD signal under DC and four types of artificial defects were fabricated to simulate typical insulation defects in GIS. The WT techniques were used to discriminate PD pulse sequences from background noise, amplitude modulation radio interference, non-sinusoidal noise, and switching impulse and the effectiveness was compared with a high-pass filter.
机译:局部放电(PD)的检测和分析已被认为是电力系统中气体绝缘结构(GIS)的条件监测和资产管理最有效的方法。然而,PD检测灵敏度和精度受到现场噪声和干扰的大大影响,导致PD严重性评估,缺陷识别或本地化中的故障。尽管在AC下的PD信号进行了脱模,但尚未进行DC下的相关调查。随着HVDC技术的快速发展,在DC下消除PD信号的噪声是一种新的挑战,用于诊断相关电力设施。因此,本文涉及基于小波变换(WT)技术HVDC GIS的PD信号的辨别,旨在提高绝缘诊断的灵敏度和准确性。实验设置被配置为在DC下产生PD信号,并制造四种类型的人工缺陷以模拟GIS中的典型绝缘缺陷。 WT技术用于区分从背景噪声,幅度调制无线电干扰,非正弦噪声和切换脉冲的PD脉冲序列,并且将有效性与高通滤波器进行比较。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号