METHOD OF EARTH FAULT LOOP IMPEDANCE MEASUREMENT WITHOUT NUISANCE TRIPPING OF RCDs IN 3-PHASE LOW-VOLTAGE CIRCUITS

机译:接地故障回路阻抗测量的方法,无需衰退3相低压电路中的RCD

获取原文
           

摘要

Verification of electrical safety in low-voltage power systems includes the measurement of earth fault loop impedance. This measurement is performed to verify the effectiveness of protection against indirect contact. The widespread classic methods and meters use a relatively high value of the measuring current (520) A, so that they are a source of nuisance tripping of residual current devices (RCDs). The meters dedicated to circuits with RCDs usually use an extremely low value of current (lower than 15 mA), which in many cases it is not acceptable in terms of the measurement accuracy. This paper presents a method of earth fault loop impedance measurement in 3-phase circuits, without nuisance tripping of RCDs - the concept of measurement, the meter structure and the experimental validation. The nuisance tripping is avoided in spite of the use of measuring current value many times higher than that of the rated residual current of RCDs. The main advantage of the proposed method is the possibility of creating values of measuring current in a very wide range, what is very important with regard to accuracy of the measurement.
机译:低压电力系统中电气安全的验证包括地球故障回路阻抗的测量。执行该测量以验证防止间接接触的有效性。广泛的经典方法和仪表使用测量电流(520)A的相对高值,使得它们是残留电流设备(RCD)的滋扰跳闸源。专用于带RCD的电路的仪表通常使用极低的电流值(低于15 mA),这在许多情况下,在测量精度方面是不可接受的。本文提出了一种在3相电路中接地故障回路阻抗测量方法,无需衰退,RCD跳闸 - 测量概念,仪表结构和实验验证。尽管使用比RCD的额定残留电流高多倍的测量电流值,避免了滋扰跳闸。所提出的方法的主要优点是在非常广泛的范围内产生测量电流值的可能性,关于测量的准确性非常重要。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号