Based on air clearance discharge characteristic curve and insulation coordination method, it is pointed out that the minimum air clearance of 1000 kV ultra-high voltage (UHV) AC substation can be further optimised. On the basis of analysis of the merits and demerits of the two insulation coordination methods for air clearances of UHV substation stated in the national standard GB/Z 24842–2009, it is concluded that using statistical method for insulation coordination is more reasonable and feasible. The minimum air clearance of UHV substation is optimised with the statistical method based on 1000 μs switching impulse characteristic test results. According to the study results, the phase-to-earth air clearance A1′ can be 1 m less than that specified in standard, the air clearance between conductors 0.5 m less than that specified in standard, and the phase-to-phase air clearance of grading ring and tubular bus 0.6 and 1.8 m, respectively, less than that specified in standard.
机译:基于空气清除放电特性曲线和绝缘配合方法,指出,可以进一步优化1000kV超高电压(UHV)AC变电站的最小空气间隙。在分析国家标准GB / Z 24842-2009中规定的UHV变电站的空气间空气间隙的两个绝缘配合方法的分析的基础上,得出结论,利用用于绝缘配位的统计方法更合理和可行。通过基于1000μs开关的脉冲特性测试结果,通过统计方法进行了优化了UHV变电站的最小空气清除。根据研究结果,相对地空气清除率A1'可以比标准规定的1米,导体之间的空气间隙比标准标准规定的4.5米,以及相位到相空气清除分级环和管状总线0.6和1.8 m,分别小于标准规定的。