In order to explore the partial discharge characteristics of 10 kV XLPE insulated cable (hereinafter referred to as ‘XLPE cable’), first six typical defects are made on the main insulation according to the requirements of the installation process and the key process in which quality problem easily occur. They are: The main insulation has a dent, the main insulation has a knife wound, the main insulation has a metal tip, the main insulation surface has impurities, the high voltage end has a metal tip, and the stripping of the semi-conductive fracture is irregular. Then, the voltage step up test is carried out, and the test is monitored by the local discharge detection system. The test results show that the typical defects caused by the installation of 10 kV XLPE cable joint will produce serious local discharge phenomenon, and the initial discharge voltage is low and the stable discharge quantity is large.
机译:为了探索10 kV XLPE绝缘电缆的局部放电特性(下文中称为“XLPE电缆”),根据安装过程的要求和质量的关键过程,在主绝缘和质量的关键过程上进行前六种典型缺陷问题很容易发生。它们是:主要绝缘具有凹痕,主绝缘具有刀伤,主绝缘具有金属尖端,主绝缘表面具有杂质,高压端具有金属尖端,并剥离半导电骨折不规则。然后,执行电压升压测试,并通过局部放电检测系统监测测试。测试结果表明,由10kV XLPE电缆接头安装引起的典型缺陷将产生严重的局部放电现象,初始放电电压低,稳定的放电量大。