Studies on Steam Absorption Chillers Performance at a Cogeneration Plant

机译:热电厂热吸收式冷水机组性能研究

获取原文
           

摘要

Absorption chillers at cogeneration plants generate chilled water using steam supplied by heat recovery steam generators. The chillers can be of either single-effect or double effect configuration and the coefficient of performance (COP) depends on the selection made. The COP varies from 0.7 to 1.2 depending on the types of chillers. Single effect chillers normally have COP in the range of 0.68 to 0.79. Double effect chillers COP are higher and can reach 1.2. However due to factors such as inappropriate operations and maintenance practices, COP could drop over a period of time. In this work the performances of double effect steam absorption chillers at a cogeneration plant were studied. The study revealed that during the period of eleven years of operation the COP of the chillers deteriorated from 1.25 to 0.6. Regression models on the operation data indicated that the state of deterioration was projected to persist. Hence, it would be recommended that the chillers be considered for replacement since they had already undergone a series of costly repairs.
机译:热电联产厂的吸收式冷却器利用热量回收蒸汽发生器提供的蒸汽产生冷冻水。冷水机可以是单效配置或双效配置,性能系数(COP)取决于选择的产品。 COP范围从0.7到1.2,具体取决于冷却器的类型。单效冷却器的COP通常在0.68至0.79的范围内。双效冷却器COP更高,可以达到1.2。但是,由于不适当的操作和维护实践等因素,COP可能会在一段时间内下降。在这项工作中,研究了热电联产工厂的双效蒸汽吸收式制冷机的性能。研究表明,在运行11年期间,冷水机组的COP从1.25降低到0.6。根据运行数据的回归模型表明,预计劣化状态将持续。因此,建议考虑考虑更换冷水机,因为它们已经进行了一系列昂贵的维修。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号