首页> 外文期刊>E3S Web of Conferences >Human response to the thermal indoor environment created by a radiant, and a combined radiant and convective cooling system
【24h】

Human response to the thermal indoor environment created by a radiant, and a combined radiant and convective cooling system

机译:人体对由辐射以及辐射与对流组合冷却系统产生的室内热环境的反应

获取原文
       

摘要

This study reports the main findings from a series of human subject experiments, where the subjects were exposed to the different indoor environments created by different cooling systems. The studied systems were a radiant cooling system (chilled ceiling and mixing ventilation, CCMV), and a combined radiant and convective cooling system (radiant diffuse ceiling ventilation, RDCV). The experiments were conducted in a climate chamber under controlled conditions. The climate chamber was configured as a two-person office room. 24 human subjects (12 female and 12 male) were chosen. The exposure lasted three hours and the participants were allowed to work on their own tasks (normal office work) during the exposure. The cooling load was 54 W/m~(2)and the room temperature at a reference location was kept constant at 26°C (summer conditions). The results show that under both systems, whole body thermal sensation was between slightly warm and neutral (closer to neutral with the RDCV system), and the overall thermal acceptability was almost the same for both systems (close to clearly acceptable). The satisfaction of the human subjects with the thermal environment was very close under the two systems; between satisfactory and slightly satisfactory (closer to satisfactory). Air movement acceptability (slightly higher and closer to clearly acceptable with the RDCV system) was also very close with the two systems. The results of the human subject experiments agree well with the physical measurements of the thermal indoor environment and confirm that the studied systems created very similar thermal indoor environments.
机译:这项研究报告了一系列人体实验的主要发现,其中实验对象暴露于由不同冷却系统创建的不同室内环境中。研究的系统是辐射冷却系统(冷冻天花板和混合通风,CCMV),以及辐射和对流组合冷却系统(辐射扩散天花板通风,RDCV)。实验在受控条件下的气候箱中进行。气候室配置为两个人的办公室。选择了24位人类受试者(12位女性和12位男性)。暴露持续了三个小时,参与者可以在暴露期间从事自己的任务(正常的办公室工作)。冷却负荷为54W / m 2(2),基准位置的室温保持恒定在26℃(夏季条件)。结果表明,在这两个系统下,全身的热感都介于轻微的温暖和中性之间(RDCV系统接近于中性),并且两个系统的总体热可接受性几乎相同(接近清晰可接受)。在这两种系统下,人类对热环境的满意度非常接近。在满意和稍满意之间(接近满意)。空气运动的可接受性(在RDCV系统中略高,接近清晰可接受)在两个系统中也非常接近。人体实验的结果与室内热环境的物理测量结果非常吻合,并确认所研究的系统创建了非常相似的室内热环境。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号