摘要

The performance of the wet cooling tower is significantly affected by the droplet size occurring in the rain zone. In order to effectively manage the size of these droplets, it was necessary to experimentally determine the effect of the fills of the cooling towers on droplets. Five types of cooling fillers were used for experimental measurements: 3 film fills and 2 splash fills - trickle and grid. Drop size measurements were performed using the LIF method. Histograms of droplets size were obtained from measured droplet sizes under each fill, and for each fill, the Sauter droplet diameter was then calculated. According to a theoretical analysis of a breakdown of droplets, the combinations of some fills and the effect of their surface treatment on the droplet diameter were then measured for comparison.
机译:湿式冷却塔的性能受雨区中出现的液滴尺寸的影响很大。为了有效地管理这些液滴的尺寸,有必要通过实验确定冷却塔的填充物对液滴的影响。五种类型的冷却填料用于实验测量:3种薄膜填料和2种飞溅填料-滴流和网格。使用LIF方法进行液滴尺寸的测量。从每个填充下测得的液滴尺寸获得液滴尺寸的直方图,然后针对每个填充量计算Sauter液滴直径。根据液滴分解的理论分析,然后测量一些填充物的组合及其表面处理对液滴直径的影响,以进行比较。