首页> 外文期刊>Journal of Power and Energy Engineering >Transmission Lines Distance Protection Using Differential Equation Algorithm and Hilbert-Huang Transform
【24h】

Transmission Lines Distance Protection Using Differential Equation Algorithm and Hilbert-Huang Transform

机译:基于微分方程算法和希尔伯特-黄变换的输电线路距离保护

获取原文
           

摘要

This paper proposed the scheme of transmission lines distance protection based on differential equation algorithms (DEA) and Hilbert-Huang transform (HHT). The measured impedance based on EDA is affected by various factors, such as the distributed capacitance, the transient response characteristics of current transformer and voltage transformer, etc. In order to overcome this problem, the proposed scheme applies HHT to improve the apparent impedance estimated by DEA. Empirical mode decomposition (EMD) is used to decompose the data set from DEA into the intrinsic mode functions (IMF) and the residue. This residue has monotonic trend and is used to evaluate the impedance of faulty line. Simulation results show that the proposed scheme improves significantly the accuracy of the estimated impedance.
机译:提出了基于微分方程算法(DEA)和希尔伯特-黄(HHT)变换的输电线路距离保护方案。基于EDA的测量阻抗受各种因素的影响,例如分布电容,电流互感器和电压互感器的瞬态响应特性等。为克服此问题,建议的方案采用HHT来改善由数据包络分析。经验模式分解(EMD)用于将DEA中的数据集分解为固有模式函数(IMF)和残差。该残留物具有单调趋势,用于评估故障线路的阻抗。仿真结果表明,该方案显着提高了估计阻抗的准确性。