Saturation is a condition in which the magnets are fully transformer cores and generate maximum magnetic flux. Some parts affect the resilience and create distortions that can harm the heart. Core saturation can also increase the temperature and magnetization current transformer. In this study, we proposed a measurement method to obtain the necessary parameters to calculate a reliable indicator of the state of the transformer core saturation. The main effects of nonlinear flow in the transformer core are saturation, eddy current and hysteresis. In saturation, the core transformer is as a source of generating harmonic currents, some of which will flow directly to the primary and secondary windings. The method is based on the magnetization current, the phenomenon of harmonics and power factor is evaluated by measuring the no-load current at three-phase transformer, with a high magnetic flux density imposed. Measurements were taken at each phase of the transformer core. The transformer is connected to a variable voltage variable frequency (VVVF) as a voltage source and the investigation carried out at various flux densities. The results showed that the magnetization current and harmonic phenomena increased significantly when the high magnetic flux density and vice versa injected with power factor declined sharply. This phenomenon can be used as an indication of saturation of the 3-phase transformer core.
机译:饱和是指磁体完全是变压器铁芯并产生最大磁通量的条件。有些零件会影响弹性,并产生会伤害心脏的变形。铁心饱和还会增加温度和磁化电流互感器。在这项研究中,我们提出了一种测量方法来获得必要的参数,以计算出变压器铁芯饱和状态的可靠指标。变压器铁心中非线性流动的主要影响是饱和度,涡电流和磁滞。在饱和状态下,铁心变压器用作产生谐波电流的源,其中一些谐波电流将直接流向初级和次级绕组。该方法基于磁化电流,通过测量三相变压器的空载电流来评估谐波现象和功率因数,并施加较高的磁通密度。在变压器铁心的每一相进行测量。变压器连接到可变电压可变频率(VVVF)作为电压源,并在各种磁通密度下进行检查。结果表明,当高磁通密度注入功率因数急剧下降时,磁化电流和谐波现象显着增加,反之亦然。该现象可以用作三相变压器铁芯饱和的指示。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号