Protection Coordination in Microgrid UsingFault Current Limiters

机译:使用故障电流限制器的微电网中的保护协调

获取原文

摘要

To ensure the seamless working of the microgrid, another Smart Grid tool- the Fault current limiter (FCL) has been proposed to suppress the fault currents to the level such that the requisite protection coordination is possible. The FCL suppresses the fault currents from the utility grid and acts as a solution to the directional overcurrent relay coordination problem within the microgrid. The FCLs are unique in the way that they are ‘invisible’ during the normal un-faulted operation of the power system but come into picture at the time of fault. The contributing reactance from the FCL is instrumental in reducing the fault currents flowing inside the microgrid from the incoming transmission feeder during the time of fault. In this paper reactance FCLs are only being used for coordination of directional overcurrent relay (DOCR) settings. Symmetrical three phase faults are considered for relay coordination. The distributed generation (DG) considered here is the conventional synchronous generator directly connected to the medium voltage networks. The proposed solution is tested on a radial distribution system (the benchmark Canadian distribution system model) of 9 bus which is adequately connected to DGs within the microgrid. Further investigation of the proposed method has been carried out for three configurations i.e grid connected, islanded and dual. It is observed from the simulation results that the operating times of relays in the grid connected configuration are similar to the operating times of the relays in the islanded mode when the optimal settings are done for the dual configuration mode and the optimizer is unable to find out any setting for both configurations without the help of FCL in the incoming feeder within the given range of relay settings.
机译:为了确保微电网的无缝运行,已经提出了另一种智能电网工具-故障电流限制器(FCL),以将故障电流抑制到一定水平,从而可以进行必要的保护协调。 FCL抑制了来自公用电网的故障电流,并作为微电网内定向过流继电器协调问题的解决方案。 FCL的独特之处在于,它们在电力系统正常无故障运行期间是“不可见的”,但在出现故障时才可见。 FCL的贡献电抗有助于减少故障期间从传入的输电馈线流入微电网内部的故障电流。在本文中,电抗FCL仅用于协调方向性过电流继电器(DOCR)设置。考虑对称的三相故障以进行继电器协调。这里考虑的分布式发电(DG)是直接连接到中压网络的常规同步发电机。所提出的解决方案在9总线的径向配电系统(基准加拿大配电系统模型)上进行了测试,该系统已充分连接到微电网中的DG。对于三种配置,即并网,孤岛和双网,已经对所提出的方法进行了进一步的研究。从仿真结果可以看出,当为双配置模式进行了最佳设置并且优化器无法找出时,并网配置中的继电器的工作时间与孤岛模式中的继电器的工作时间相似。在给定的继电器设置范围内,两种配置的任何设置都无需输入馈线中的FCL帮助。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号