This article focuses on validating a time-domain power system protection solution, based on energy and reactive power algorithms, through simulations using hardware-in-the-loop. The results are compared against a commercial, off-the-shelf, intelligent electronic device. The developed protection algorithms are briefly described, followed by the description of the hardware platform responsible for its practical execution and the description of the applied tests. The obtained results show significant advantages on response times when compared to traditional protection, and the ability to securely identify delicate internal transformer faults, even during inrush condition.
机译:本文着重于通过基于硬件在环的仿真,基于能源和无功功率算法,验证时域电力系统保护解决方案。将结果与商用现成的智能电子设备进行比较。简要描述了开发的保护算法,然后描述了负责其实际执行的硬件平台以及所应用测试的描述。与传统保护相比,所获得的结果显示出在响应时间上的显着优势,即使在浪涌条件下,也能够安全地识别出变压器内部的细微故障。