This paper presents the performance analysis of a window air conditioner unit incorporated with wick less loop heat pipes (WLHP). The WLHP are located on the evaporator side of the air conditioning unit. The working medium for the WLHP is R134a refrigerant gas, an alternate refrigerant. The supply and return humidity of room air, the heat removal rat, and the coefficient of performance of the unit are analyzed for various ambient and room temperatures before and after incorporation of WLHP. The performance curves are drawn by comparing the power consumption and humidity collection rates for various room and ambient temperatures. The results show that coefficient of performance of the unit is improved by 18% to 20% after incorporation of WLHP due to pre-cooling of return air by WLHP, which reduces the thermal load on compressor. Similarly, the energy consumption is reduced by 20% to 25% due to higher thermostat setting and the humidity collection is improved by 35% due to pre-cooling effect of WLHP. The results are tabulated and conclusion drawn is presented based on the performance.
机译:本文介绍了装有无芯吸热管(WLHP)的窗户空调装置的性能分析。 WLHP位于空调单元的蒸发器侧。 WLHP的工作介质是R134a制冷剂气体,一种替代制冷剂。在掺入WLHP之前和之后,针对各种环境和室温,分析了室内空气的供给和返回湿度,除热率以及设备的性能系数。通过比较各种室温和环境温度下的功耗和湿度收集率来绘制性能曲线。结果表明,由于采用WLHP对回风进行了预冷却,因此引入WLHP后,该装置的性能系数提高了18%至20%,从而降低了压缩机的热负荷。同样,由于较高的恒温器设置,能耗降低了20%至25%,而WLHP的预冷却效果使湿度收集提高了35%。将结果制成表格并根据性能给出结论。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号