首页> 外文期刊>Modern Applied Science >Evaluation of a Cooling Performance of a Typical Full Loaded Cool Storage Using Mono-scale CFD Simulation
【24h】

Evaluation of a Cooling Performance of a Typical Full Loaded Cool Storage Using Mono-scale CFD Simulation

机译:使用单尺度CFD仿真评估典型满负荷蓄冷库的制冷性能

获取原文
       

摘要

A mono-scale three-dimensional validated CFD model was developed to predict airflow, heat and mass transfer in order to evaluate the cooling performance of a typical full loaded cool storage. The bottom of the room was subjected to fresher and cooler air with relatively higher velocity, therefore the product’s temperature reduced from top to bottom (at least from 288 to 286.21 ?k) as well as from left to right (at least from 289.91 to 283.86 ?k). The averaged absolute deviation of product’s temperature varied versus cooling time and reached to the maximum of 2.1 ?C between the 7 and 9th hours of cooling time and 0.7 ?C at the end of cooling process. Between 5.5 to 9.5 ?C difference was observed between the hottest and coolest product’s temperature during the cooling time. The model predicted the average weight loss of 1.85% for apple during the six months period in cool storage.
机译:为了评估典型的满负荷蓄冷库的冷却性能,开发了经单维度三维验证的CFD模型以预测气流,热量和质量传递。房间的底部以相对较高的速度经受新鲜和凉爽的空气,因此产品的温度从上到下(至少从288降至286.21?k)以及从左到右(至少从289.91降至283.86)降低。 ?k)。产品温度的平均绝对偏差随冷却时间的变化而变化,在冷却时间的第7至9小时达到最高2.1℃,在冷却过程结束时达到0.7℃。在冷却期间,观察到最热和最冷产品的温度之间存在5.5至9.5°C的差异。该模型预测,冷藏六个月期间苹果的平均体重减轻了1.85%。