Dissolved gas analysis (DGA) has been widely applied to diagnose internal faults in transformer insulation systems. However, the accuracy of DGA technique is limited because of the lack of positive correlation of the fault-identifying gases with faults found in power transformers. This paper presents a laboratory study on the correlation between oil dissolved gas formation and partial discharge (PD) statistical parameters. Canonical correlation analysis (CCA) is employed to explore the underlying correlation and to extract principal feature parameters and gases in the development of different PD defects. This study is aimed to provide more information in assisting the separation, classification and identification of PD defects, which might improve the existing transformer dissolved gas analysis (DGA) schemes. An application of a novel ratio method for discharge diagnosis is proposed. The evaluation of DGA data both in laboratory and actual transformers proves the effectiveness of the method and the correlation investigation.
机译:溶解气体分析(DGA)已广泛应用于诊断变压器绝缘系统中的内部故障。但是,由于故障识别气体与电力变压器中的故障之间缺乏正相关,因此DGA技术的准确性受到限制。本文对油溶气形成与局部放电(PD)统计参数之间的相关性进行了实验室研究。典型相关分析(CCA)用于探索潜在的相关性,并提取不同PD缺陷发展过程中的主要特征参数和气体。这项研究旨在为辅助PD缺陷的分离,分类和识别提供更多信息,这可能会改善现有的变压器溶解气体分析(DGA)方案。提出了一种新颖的比率法在放电诊断中的应用。在实验室和实际变压器中对DGA数据的评估证明了该方法和相关研究的有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号