Second Law Analysis of a Mobile Air Conditioning System with Internal Heat Exchanger Using Low GWP Refrigerants

机译:具有低全球升温潜能值制冷剂的带有内部热交换器的移动空调系统的第二定律分析

获取原文
   

获取外文期刊封面封底 >>

       

摘要

This paper investigates the results of a Second Law analysis applied to a mobile air conditioning system (MACs) integrated with an internal heat exchanger (IHX) by considering R152a, R1234yf and R1234ze as low global warming potential (GWP) refrigerants and establishing R134a as baseline. System simulation is performed considering the maximum value of entropy generated in the IHX. The maximum entropy production occurs at an effectiveness of 66% for both R152a and R134a, whereas for the cases of R1234yf and R1234ze occurs at 55%. Sub-cooling and superheating effects are evaluated for each one of the cases. It is also found that the sub-cooling effect shows the greatest impact on the cycle efficiency. The results also show the influence of isentropic efficiency on relative exergy destruction, resulting that the most affected components are the compressor and the condenser for all of the refrigerants studied herein. It is also found that the most efficient operation of the system resulted to be when using the R1234ze refrigerant.
机译:本文通过将R152a,R1234yf和R1234ze视为低全球变暖潜能(GWP)制冷剂并将R134a确立为基准,研究了应用于内部热交换器(IHX)的移动空调系统(MAC)的第二定律分析结果。考虑IHX中生成的熵的最大值进行系统仿真。对于R152a和R134a,最大熵产生的发生率均为66%,而对于R1234yf和R1234ze的情况,发生率为55%。对于每种情况,都会评估过冷和过热效果。还发现过冷效应对循环效率显示出最大的影响。结果还显示了等熵效率对相对火用破坏的影响,导致受影响最大的组件是本文研究的所有制冷剂的压缩机和冷凝器。还发现系统的最有效运行是使用R1234ze制冷剂时。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号