This paper describes the advantages and disadvantages of a generator differential protection relay system which uses double slope characteristics of Areva P343, ABB REG670, SEL300G and GE G60. A Buon Tua Srah Hydropower Plant in Vietnam was selected as an example for the relay setting calculations of these characteristics. The performance of the introduced relay model was tested at various fault conditions in Matlab/Simulink. The results apply to the problems of solving the performance of the relay accurately and with reliable differential protection against internal faults, and keeping the generator stable on all external faults and in normal conditions. The simulation simplifies the process of selecting the relay and protection system. This can improve the quality of the protection system design early, thereby reducing the number of errors found later in the operation.
机译:本文介绍了一种发电机差动保护继电系统的优缺点,该系统利用Areva P343,ABB REG670,SEL300G和GE G60的双斜率特性。选择了越南的Buon Tua Srah水力发电厂作为这些特征的继电设定计算的示例。在Matlab / Simulink中的各种故障条件下,对引入的继电器模型的性能进行了测试。该结果适用于以下问题:精确地解决继电器的性能以及对内部故障提供可靠的差动保护,并在所有外部故障和正常条件下保持发电机稳定的问题。该仿真简化了选择继电器和保护系统的过程。这样可以尽早提高保护系统设计的质量,从而减少以后在操作中发现的错误数量。