首页> 外文期刊>Energy and power engineering >Detection of Mechanical Deformation in Old Aged Power Transformer Using Cross Correlation Co-Efficient Analysis Method
【24h】

Detection of Mechanical Deformation in Old Aged Power Transformer Using Cross Correlation Co-Efficient Analysis Method

机译:基于互相关系数分析法的老式电力变压器机械变形检测

获取原文
           

摘要

Detection of minor faults in power transformer active part is essential because minor faults may develop and lead to major faults and finally irretrievable damages occur. Sweep Frequency Response Analysis (SFRA) is an effective low-voltage, off-line diagnostic tool used for finding out any possible winding displacement or mechanical deterioration inside the Transformer, due to large electromechanical forces occurring from the fault currents or due to Transformer transportation and relocation. In this method, the frequency response of a transformer is taken both at manufacturing industry and concern site. Then both the response is compared to predict the fault taken place in active part. But in old aged transformers, the primary reference response is unavailable. So Cross Correlation Co-Efficient (CCF) measurement technique can be a vital process for fault detection in these transformers. In this paper, theoretical background of SFRA technique has been elaborated and through several case studies, the effectiveness of CCF parameter for fault detection has been represented.
机译:检测电力变压器有源部件中的小故障至关重要,因为可能会发生小故障并导致大故障,并最终导致无法挽回的损害。扫频响应分析(SFRA)是一种有效的低压离线诊断工具,用于发现由于故障电流产生的较大的机电力或由于变压器的运输以及搬迁。在这种方法中,变压器的频率响应在制造行业和相关场所都需要。然后将两个响应进行比较,以预测发生在活动部件中的故障。但是在老式变压器中,主要的参考响应不可用。因此,互相关系数(CCF)测量技术可能是这些变压器中故障检测的重要过程。本文阐述了SFRA技术的理论背景,并通过案例研究,阐述了CCF参数在故障检测中的有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号