首页> 外文期刊>ire Science and Technology >Tenability Analysis of Television Set Fires in a Sprinkler Protected Compartment
【24h】

Tenability Analysis of Television Set Fires in a Sprinkler Protected Compartment

机译:喷淋保护室电视火灾的持久性分析

获取原文
       

摘要

References(30) This paper describes an evaluation of the performance of a fast response residential sprinkler system in a simulated apartment in the event of a fire caused by a burning television set. The evaluation was conducted in an 8m × 4m × 2.4m high gypsum plasterboard lined compartment. A 1.2 m2 lobby was used to represent an adjoining room and a standard hollow core door connected the two spaces. The compartment was fitted with two pendent mounted fast response residential sprinkler heads, and the television sets were located in one corner of the compartment. A series of 21 tests was conducted using a tea light candle against the outside of the television casing as the ignition source. Gas analysis for CO, CO2, O2 was carried out along with measurements of visual obscuration, compartment temperature and mass loss of the fuel. Tenability conditions within the compartment were determined using Fractional Effective Dose calculations. The results showed that the sprinkler system did not respond well to the television fires. Conditions within the compartment approached or exceeded tenable limits on a number of occasions. In some instances the television set burned out completely without activating the sprinkler system.
机译:参考文献(30)本文描述了在电视机烧毁引起火灾的情况下,对模拟公寓中快速响应住宅洒水系统的性能进行评估。评估是在8m×4m×2.4m高石膏石膏板衬砌隔间中进行的。一个1.2平方米的大厅用来代表一个相邻的房间,一个标准的空心门将两个空间连接起来。隔室装有两个悬垂安装的快速响应住宅喷头,电视机位于隔室的一个角落。使用茶蜡对电视外壳的外部作为点火源进行了21项测试。进行了CO,CO2,O2的气体分析,并进行了视线模糊,车厢温度和燃料质量损失的测量。使用分数有效剂量计算确定隔室中的韧性条件。结果表明,洒水系统对电视火灾反应不佳。车厢内的情况在许多情况下接近或超过了可忍受的极限。在某些情况下,电视机没有启动喷水灭火系统就完全烧坏了。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号