The objective of this research was to study the effects of highly moist inlet air conditions such as temperature, relative humidity, and frontal air velocity on the value of the Lewis number (Le) in the cooling and dehumidifying process of air. A finned tube cooling coil was tested under ranges of temperature, relative humidity and frontal velocity. It was found that the Lewis number (Le) varied within the range of 0.92-1.62 and that the increase in inlet air relative humidity tends to decrease the Lewis number (Le). Based on the experimental, a correlation for predicting the Lewis number (Le) was also established in this article. The correlation has the mean absolute error (MAE) of 3.04% and covers 98.07% of the data where a discrepancy within ± 10%.
机译:这项研究的目的是研究在空气冷却和除湿过程中,高度潮湿的进气条件(例如温度,相对湿度和正面风速)对路易斯数(Le)值的影响。在温度,相对湿度和正面速度的范围内测试了翅片管冷却盘管。发现路易斯数(Le)在0.92-1.62的范围内变化,并且进气相对湿度的增加趋向于降低路易斯数(Le)。基于实验,本文还建立了预测路易斯数(Le)的相关性。相关具有3.04%的平均绝对误差(MAE),覆盖了98.07%的数据,其中差异在±10%以内。