In modern digital power system protection systems, statistical coefficients technique is recently used for fault analysis. An alienation technique is developed for busbar protection against all ten types of shunt faults, which may locate in busbar protection zone, under different loading levels, fault resistances and fault inception angle. It does not need any extra equipment as it depends only on the three-line currents measurements, of all feeders connected to the protected busbar, which are mostly available at the relay location. It is able to perform fault detection, fault confirmation, faulty phase selection and determine the fault location in about a half-cycle period. Thus, the alienation technique is well suited for implementation in digital protection schemes. The technique is efficient to detect current transformer saturation conditions without needing any additional algorithm. The effects of DC components and harmonics are eliminated with estimation of alienation coefficients. The proposed methodology is applied for a part of 500 KV Egyptian network. Alternative transient program (ATP) and MATLAB package are used to implement the proposed technique.
机译:在现代数字电源系统保护系统中,统计系数技术最近用于故障分析。开发了一种针对所有十种分路故障的母线保护异化技术,这些故障可能位于母线保护区内,处于不同的负载水平,故障电阻和故障起始角度。它不需要任何额外的设备,因为它仅取决于连接到受保护母线上的所有馈线的三线电流测量值,这些馈线大多数都位于继电器位置。它能够执行故障检测,故障确认,故障相位选择并在大约半个周期内确定故障位置。因此,疏离技术非常适合在数字保护方案中实施。该技术可以有效地检测电流互感器的饱和条件,而无需任何其他算法。直流分量和谐波的影响可通过估算异化系数来消除。所建议的方法适用于500 KV埃及网络的一部分。可选的瞬态程序(ATP)和MATLAB程序包用于实现所提出的技术。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号