The numerical simulation and experimental study on rack cooling effect in date center with UFAD system

机译:UFAD系统对数据中心机架散热效果的数值模拟与实验研究

获取原文
   

获取外文期刊封面封底 >>

       

摘要

In order to analyze the way of improving the cooling effect of the data center with the UFAD system, the HVAC simulation software—Airpak—was applied. Numerical simulations for the interior temperature of the rack at different porosity ratios were carried out, and the simulated results indicate that the way of partly enhancing the porosity ratio of the front door and back door can improve the cooling effect. To solve the issue of the thermal current recycle in the exhaust outlet and airflow distribution disorder, the measure of the cold aisle regional closure was taken, and the comparison of data before and after the closure of the cold aisle proved its positive influence on the cooling effect: to lowering the inlet air temperature of racks, to improve airflow distribution inside and outside of the rack and to solve the thermal current recycle in the exhaust outlet.
机译:为了分析使用UFAD系统改善数据中心散热效果的方法,应用了HVAC仿真软件Airpak。对不同孔隙率的机架内部温度进行了数值模拟,仿真结果表明,部分提高前门和后门的孔隙率的方法可以提高冷却效果。为解决排气口热流循环和气流分布紊乱的问题,采取了冷通道区域封闭的措施,对冷通道封闭前后的数据进行比较,证明了其对冷却的积极影响。效果:降低机架的进气温度,改善机架内部和外部的气流分布,并解决排气口中的热循环。