ESTIMATION OF VERY FAST TRANSIENT OVER VOLTAGES ON BUSHING CONNECTED IN GIS

机译:GIS中连接的套管上非常快速的瞬时过电压估算

获取原文
           

摘要

In a number of GIS installations, the connection to the transformer is given through either SF6 / air bushing or SF6 / oil bushing. The VFTO generated internal to GIS may propagate to the transformer winding through the above capacitive graded bushing (generally 245 KV and above). The voltage distribution under very fast transients may be highly non-linear due to having frequency components in the range of 100 MHz and above. Further, continuous application of these oscillating, aperiodic over voltages to the capacitively graded bushing may cause discharges inside the bushing, which may progressively degrade its insulation strength. The voltage distribution across various layers of capacitively graded bushing has been estimated by representing the layers as an equivalent multi-stage ? sections with Pspice
机译:在许多GIS安装中,通过SF6 /空气套管或SF6 /油套管来提供与变压器的连接。 GIS内部生成的VFTO可能会通过上述电容分级套管(通常为245 KV及以上)传播到变压器绕组。由于频率分量在100 MHz或更高的范围内,因此非常快速的瞬态下的电压分布可能会高度非线性。此外,将这些振荡的,非周期性的过电压连续施加到电容梯度套管上可能导致套管内部的放电,这可能会逐渐降低其绝缘强度。通过将各层表示为等效的多级φ,可以估算出电容梯度套管各层之间的电压分布。 Pspice的内容