首页> 外文期刊>Archives of Thermodynamics >Dependence of the boiler flue gas losses on humidity of wood biomass
【24h】

Dependence of the boiler flue gas losses on humidity of wood biomass

机译:锅炉烟气损失与木材生物量湿度的关系

获取原文
           

摘要

The paper analyzes the influence of humidity of combusted wood biomass on the flue gas losses. A mathematical relation between flue gas losses of the boiler on wood biomass humidity is presented as well as temperature of flue gas emitted from the boiler into the atmosphere. The limits of model application for the humidity of wood biomass falls into the interval 10a€“60% whereas the range of temperatures of flue gases emitted from the boiler to the atmosphere is 120a€“200 ?°C. The influence of the humidity of wood biomass has an adverse effect on increasing the extent of the boiler flue gas losses and thus inefficiency of the heat production. The increase of the wood biomass humidity from the value of 10% to 60% with the outlet temperature of flue gases from the boiler 120 ?°C causes an increase in flue gas loss of the boiler from the value 8.37% to 12.43%, similarly the increase of flue gas loss by 200 ?°C from 15.19% to 22.55%, or the increase of the flue gas loss by 7.36%.
机译:本文分析了燃烧过的木材生物量的湿度对烟气损失的影响。给出了锅炉烟气损失与木材生物量湿度之间的数学关系,以及从锅炉排放到大气中的烟气温度的数学关系。木材生物量湿度的模型应用范围限制在10%至60%之间,而从锅炉排放到大气的烟道气温度范围为120%至200°C。木材生物量的湿度的影响对增加锅炉烟气损失的程度具有不利影响,并因此不利于热量产生。随着锅炉烟气出口温度的升高,木材生物量湿度从10%升高到60%,导致锅炉烟气损失从8.37%增加到12.43%。烟气损失增加200°C,从15.19%增加到22.55%,烟气损失增加7.36%。