首页> 外文期刊>Archives of Thermodynamics >Absorption and adsorption chillers applied to air conditioning systems
【24h】

Absorption and adsorption chillers applied to air conditioning systems

机译:吸收式和吸附式冷却器应用于空调系统

获取原文
   

获取外文期刊封面封底 >>

       

摘要

This work presents an application possibility of sorption refrigerators driven by low temperature fluid for air conditioning of buildings. Thermodynamic models were formulated and absorption LiBr-water chiller with 10 kW cooling power as well as adsorption chiller with silica gel bed were investigated. Both of them are using water for desorption process with temperature Tdes = 80 °C. Coefficient of performance (COP) for both cooling cycles was analyzed in the same conditions of the driving heat source, cooling water Tc = 25 °C and temperature in evaporator Tevap = 5 °C. In this study, the computer software EES was used to investigate the performance of absorption heat pump system and its behaviour in configuration with geothermal heat source.
机译:这项工作提出了由低温流体驱动的吸附式制冷机在建筑物空调中的应用可能性。建立了热力学模型,研究了功率为10 kW的吸收式溴化锂冷水机以及带硅胶床的吸附式冷水机。他们俩都使用水进行解吸工艺,温度为Tdes = 80°C。在驱动热源,冷却水Tc = 25°C和蒸发器温度Tevap = 5°C的相同条件下,分析了两个冷却循环的性能系数(COP)。在这项研究中,使用计算机软件EES来研究吸收式热泵系统的性能及其在地热热源配置下的行为。