首页> 外文期刊>Civil and Environmental Research >Case Study of Seismic Effect on Hyperbolic Cooling Towers
【24h】

Case Study of Seismic Effect on Hyperbolic Cooling Towers

机译:双曲冷却塔的地震效应实例研究

获取原文

摘要

This paper deals with the study of seismic analysis of hyperbolic cooling towers. Two existing cooling towers are chosen from Bellary thermal power station (BTPS) as case study. FEA based ANSYS Software is used for the analysis. The boundary conditions considered are Top end free and Bottom end fixed. The material properties of the cooling tower are young’s modulus 31GPa, Poisson’s Ratio 0.15 and density of RCC 25 kN/m3. The analysis is carried out using 8 noded SHELL 93 element. Maximum deflection, Maximum Principal Stress & Strain, Maximum Von Mises Stress, Strains are obtained. The variation in max principal stress v/s thickness, maximum deflection v/s thickness is plotted graphically.
机译:本文涉及双曲线冷却塔的地震分析研究。案例研究从Bellary热电站(BTPS)中选择了两个现有的冷却塔。基于FEA的ANSYS软件用于分析。考虑的边界条件是自由上端和固定下端。冷却塔的材料特性是杨氏模量31GPa,泊松比0.15和RCC密度25 kN / m3。使用8节点SHELL 93元素进行分析。获得最大挠度,最大主应力和应变,最大冯米塞斯应力,应变。最大主应力v / s厚度,最大挠度v / s厚度的变化以图形方式绘制。