首页> 外文期刊>Buildings >Field Observation of Cooling Energy Savings Due to High-Reflectance Paints
【24h】

Field Observation of Cooling Energy Savings Due to High-Reflectance Paints

机译:高反射率涂料在冷却节能方面的现场观察

获取原文
           

摘要

Cooling energy savings in a building with the roof coated with high-reflectance paint are examined. It is difficult to recognize such savings using the data observed hourly. Among the factors assumed to affect cooling energy load are: (1) internal heat generation, (2) set temperature, and (3) weather conditions. By analyzing the relationship between indoor-outdoor air temperature difference (averaged) and electric power consumption (integrated) of the air conditioner in the building over a day, the reduction in electric power consumption due to the use of a high-reflectance paint coating is estimated at approximately 72 Wh·m−2·day−1.
机译:研究了屋顶涂有高反射涂料的建筑物的冷却节能效果。使用每小时观察到的数据很难识别这种节省。假定会影响冷却能量负荷的因素包括:(1)内部发热,(2)设定温度和(3)天气条件。通过分析一天中建筑物内室内外空气温度差(平均)与空调器的电力消耗(综合)之间的关系,可以发现由于使用了高反射率涂料而减少的电力消耗估计约为72 Wh·m -2 ·天 -1