首页> 外文期刊>Building Services Engineering Research & Technology >Noise levels and noise sources in acute care hospital wards
【24h】

Noise levels and noise sources in acute care hospital wards

机译:急诊医院病房的噪音水平和噪音源

获取原文
获取原文并翻译 | 示例

摘要

Noise in hospital wards has the potential to slow down the recovery of patients. A comprehensive and systematic analysis of noise levels and noise sources has been carried out in two intensive care units and one high dependency unit in two Edinburgh hospitals (UK). Noise levels L_(Aeq, 1min) and L_(AFmax) were measured at 1 minute intervals for 24 hour periods, and noise sources responsible for L_(AFmax) were identified. High noise levels were found in the three wards, the lowest L_(Aeq, 1min) being measured in the modern ward tested, where an acoustic ceiling was present. A substantial number of noise sources have been observed and analysed statistically, many of which had never been identified by previous research. It was found that 34% of these are totally avoidable and 28% are partially avoidable. Noise control solutions are presented, with practical solutions affecting 48% of the noise sources, and staff education affecting 14% of the sources. Practical application: The analysis and classification of noise sources obtained has lead to the identification and presentation of practical noise control solutions, some of which can be implemented at the design stage. This is of direct relevance to building services engineers who play a role in the design of hospital wards, and can therefore use this information. It can also be noted that average and maximum noise levels measured in this study could form the basis for the development of noise guidelines in intensive care units and high dependency units, as current limits do not appear to be appropriate for such spaces.
机译:医院病房的噪音有可能减慢患者的康复速度。在两个爱丁堡医院(英国)的两个重症监护室和一个高依赖病房中,已经对噪声水平和噪声源进行了全面而系统的分析。以24分钟为间隔,每隔1分钟测量一次噪声水平L_(Aeq,1min)和L_(AFmax),并确定造成L_(AFmax)的噪声源。在三个病房中发现了很高的噪音水平,在有隔音天花板的现代病房中测得的最低L_(Aeq,1min)。已经观察到并统计地分析了大量噪声源,其中许多噪声源以前的研究从未发现过。发现其中34%是完全可以避免的,而28%是部分可以避免的。介绍了噪声控制解决方案,其中实际解决方案影响了48%的噪声源,而员工培训影响了14%的噪声源。实际应用:获得的噪声源的分析和分类导致了对实际噪声控制解决方案的识别和介绍,其中一些解决方案可以在设计阶段实施。这与在医院病房设计中发挥作用的建筑服务工程师直接相关,因此可以使用此信息。还应注意的是,本研究中测得的平均和最大噪声水平可能会成为重症监护病房和高依赖病房中制定噪声指南的基础,因为电流限制似乎不适用于此类场所。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号