首页> 外文期刊>Building and Environment >Car park ventilation system: performance evaluation
【24h】

Car park ventilation system: performance evaluation

机译:停车场通风系统:性能评估

获取原文
获取原文并翻译 | 示例
       

摘要

Unsatisfactory design of mechanical ventilation systems in car parks would give poor indoor environment. Site investigations on the ventilation systems in six car parks were carried out. Physical configurations of the car park and ventilation system installed were studied. Carbon monoxide levels were measured during the peak hours. From the results, parameters including the removal effectiveness and local air quality index were examined in conjunction with the measured carbon monoxide levels. Performance of different types of ventilation systems was compared. It is found that the combined supply and exhaust system performs better than the exhaust-only system in controlling carbon monoxide levels at occupied zones (0.5-1.5 m measured from floor level) although more energy is consumed.
机译:停车场机械通风系统的设计不理想会导致室内环境恶劣。对六个停车场的通风系统进行了现场调查。研究了停车场的物理结构和安装的通风系统。在高峰时段测量一氧化碳水平。从结果中,结合测量的一氧化碳水平检查了包括去除效果和局部空气质量指数在内的参数。比较了不同类型通风系统的性能。已经发现,尽管消耗了更多的能量,但是在供气区域(从地面水平测量的0.5-1.5 m)控制一氧化碳水平方面,组合式供气和排气系统的性能优于仅排气系统。