首页> 外文期刊>Building and Environment >Airflow performance of ventilated sub flooring system
【24h】

Airflow performance of ventilated sub flooring system

机译:通风地板系统的通风性能

获取原文
获取原文并翻译 | 示例
       

摘要

This study analyses the airflow performance of a ventilated sub-flooring system that is only 3 mm thick in laboratory and field conditions and with analytical modelling. Measurements and calculations showing good agreement were allowed to determine resultant equations for the sizing of the systems. It is shown that the design airflow keeps the floor under negative pressure, which prevents the penetration of odours and other contamination leakage to indoors. The design recommendations for ventilated sub-flooring systems are given. In the field study, the performance of the wall application of the system was shown. A quality assurance method was developed to ensure the required airflow in the ventilated sub-flooring system. Possible air leakages of the system can be found with a smoke detector and by real air-intake flow measurements to the floor made with an electronic soap film calibrator.
机译:这项研究分析了通风的地下地板系统的气流性能,该系统在实验室和野外条件下厚度仅为3 mm,并具有分析模型。允许显示出良好一致性的测量和计算来确定用于系统规模的最终方程。结果表明,设计气流使地板保持负压,从而防止了气味的渗透和其他污染物向室内的泄漏。给出了通风地下地板系统的设计建议。在现场研究中,显示了该系统的墙面应用程序的性能。开发了一种质量保证方法,以确保通风的地下地板系统中所需的气流。系统的可能漏气可以通过烟雾探测器以及通过电子肥皂膜校准器对地板的实际进气流量测量来发现。