首页> 外文期刊>Building and Environment >Tracer gas experiment for local mean ages of air from individual supply inlets in a space with multiple inlets
【24h】

Tracer gas experiment for local mean ages of air from individual supply inlets in a space with multiple inlets

机译:示踪气体实验,用于在具有多个进气口的空间中从各个进气口获得的局部平均空气年龄

获取原文
获取原文并翻译 | 示例
           

摘要

We investigate the supply characteristics of incoming air via individual inlets in a ventilated space with multiple inlets. Theoretical considerations are given to determine the relations between the local mean age (LMA) of the total supply air and the individual LMA of each supply air inlet. Tracer gas experiments are conducted in a simplified livestock model with two supply inlets and one exhaust outlet. Transient concentration responses at internal points are measured after tracer gas injection one inlet at a time, and for simultaneous tracer injection at both inlets. The spatial distributions of LMAs and steady concen-trations are obtained by tracer injections from each supply inlet, which demonstrate the supply characteristics of the individual inlets in the space. We have found that the overall LMA is the weighted average of the LMA by each inlet, and the weighting factor for the average is the corresponding steady state concentration at a given point. Experiments repeated for various airflow rates show that the nondimensional steady concentrations remain nearly constant regardless of the total airflow rate, but are greatly influenced by the airflow ratio between inlets. The local mean ages are found to increase proportionally with respect to the nominal time constant. Experimental procedures and results are verified by the fact that the total LMA measured at the exhaust is in good agreement with the theoretical nominal time constant of the space.
机译:我们研究通过通风口中具有多个进气口的单个进气口进入空气的供应特性。给出了理论上的考虑,以确定总供气的局部平均寿命(LMA)与每个供气入口的单个LMA之间的关系。在具有两个进气口和一个排气口的简化牲畜模型中进行了示踪气体实验。在一次向一个入口注入示踪气体后,在两个入口同时进行示踪剂注入之后,测量内部点的瞬态浓度响应。 LMA的空间分布和稳定浓度是通过从每个供应入口进行示踪剂注入获得的,这表明了空间中各个入口的供应特性。我们发现,总体LMA是每个入口LMA的加权平均值,而该平均值的加权因子是给定点处的相应稳态浓度。对各种气流速率重复进行的实验表明,无论总气流速率如何,无量纲的稳定浓度几乎保持恒定,但受进气口之间的气流比率的影响很大。发现本地平均年龄相对于标称时间常数成比例增加。实验程序和结果通过以下事实验证:排气处测得的总LMA与空间的理论标称时间常数高度吻合。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号