To quantify the illuminance and energy consumption levels achieved by Increasing the ceiling's light reflectance (LR), ceiling system manufacturer Armstrong World Industries commissioned Brinjac Engineering to conduct two controlled studies. (Illuminance is a measure of the intensity of light on a unit area of a surface.) In the first study, four different room configurations were outfitted with a direct recessed 2X2-foot parabolic troffer and an indirect pendant. One set of rooms was given a 75% reflective ceiling; the others, a 90% reflective ceiling, After measuring work plane illuminance in both sets of rooms, Brinjac found the 0.90 LR ceiling to increase direct lighting levels by just 2-5%; however, indirect lighting levels jumped by almost 22% and offered greater lighting uniformity.