摘要

The need to reduce operating costs of commercial uranium hexafluoride production motivates the present study. With this in mind, a variant of coolant flow reduction in the tubing of the desublimation apparatus is proposed. Mathematical calculations showed that the coolant consumption can be reduced by a factor of 2. Field experiments performed at an operating production facility have confirmed the obtained results. A combined control system has been developed to maintain the coolant flow at the minimum level and to secure the conditions of desublimation for uranium hexafluoride. The developed control system will make it possible to reduce by factor of 2 the volume of coolant consumption without loss of product quality or production volume.
机译:需要降低商业铀六氟化铀生产经营成本的需求激励本研究。考虑到这一点,提出了灭腔装置的管道中冷却剂流动减少的变型。数学计算表明,冷却剂消耗可以减少2.在操作生产设备上进行的现场实验证实了所得结果。已经开发了一种组合的控制系统以保持最小水平的冷却剂流动,并确保六氟化铀矿的脱气条件。开发的控制系统将使可以减少2个冷却剂消耗量的因数,而不会损失产品质量或产量。