首页> 外文期刊>ASHRAE Transactions >Field Study on Independent Dehumidification Air-Conditioning System—Ⅱ: Performance of the Whole System
【24h】

Field Study on Independent Dehumidification Air-Conditioning System—Ⅱ: Performance of the Whole System

机译:独立除湿空调系统的现场研究——Ⅱ:整个系统的性能

获取原文
获取原文并翻译 | 示例
           

摘要

An independent dehumidification air-conditioning system has been built in Beijing, China. The dehumidificaiton is done by a hot water-driven liquid desiccant dehumidification subsystem. This paper reports results of field measurement of the system, which shows that the system canproduce a comfortable indoor environment even in very humid weather. On dry days, the dehumidification system bears around 40% of the total load, while on humid days, it bears around 50%. Economic comparison of the independent dehumidification system and a conventional system indicates that the two systems have equivalent distribution power consumption, but the former one may save about 30% cooling source cost when the price ratio of electricity to heat is reasonably set.
机译:在中国北京建立了独立的除湿空调系统。除湿是通过热水驱动的液体干燥剂除湿子系统完成的。本文报告了该系统的现场测量结果,表明该系统即使在非常潮湿的天气下也可以产生舒适的室内环境。在干燥的日子里,除湿系统承担约40%的总负荷,而在潮湿的日子里,约占50%。独立除湿系统与常规系统的经济比较表明,这两个系统具有相等的分配功率消耗,但如果合理设定电热价格比,前者可以节省约30%的冷却源成本。