Condensation Enhancement of R-22 by Twisted-Tape Inserts Inside a Horizontal Tube

机译:水平管内的扭曲带插入物增强了R-22的冷凝

获取原文
获取原文并翻译 | 示例
           

摘要

In this paper the salient features of an experimental investigation on heat transfer enhancement by twisted-tape inserts inside a horizontal R-22 condenser are reported. The test condenser has four test sections connected in series, and each test section has an inside diameter of 12.7 mm and length of 950 mm. Three twisted-tape inserts with twist ratios, y, of 14.95, 9.05, and 5.90 were put, oneby one, in the entire length of the test condenser. The refrigerant mass velocity G was varied from 210 to 372 kg/s-m~2 in four steps. Enhancement in the average heat transfer coefficient h was attained up to 25% for the twisted-tape insert with the twist ratio y of 5.90, as compared to the plain tube flow. It was also found that the twisted-tape inserts are more effective at low vapor mass velocities inside the tubes. An empirical correlation equation was also developed to calculate the heat transfer coefficients. This equation predicts the experimental heat transfer coefficient within an error band of ± 30% for a tube with the twisted-tape inserts.
机译:在本文中,报道了水平R-22冷凝器内的扭曲带插入物增强传热的实验研究的显着特征。测试冷凝器有四个串联的测试部分,每个测试部分的内径为12.7毫米,长度为950毫米。将三个y分别为14.95、9.05和5.90的扭曲比y的扭曲胶带插入测试冷凝器的整个长度中。制冷剂质量速度G分四个步骤在210至372 kg / s-m〜2之间变化。与普通管流相比,扭曲带y的扭曲比y为5.90时,平均传热系数h的提高达到了25%。还发现扭曲带插入物在管内的低蒸汽质量速度下更有效。还建立了一个经验相关方程来计算传热系数。该方程可预测带扭曲胶带插入物的管的实验传热系数在±30%的误差带内。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号