This paper reports the response times of six different duct-mounted relative humidity transmitters used in building HVAC. Of the six transmitters, three were capacitive and the remaining three were resistive. This paper describes the test hardware used to determine the response times of relative humidity transmitters, along with a detailed description of the test conditions and the experimental test procedure. The experimental test results revealed significant variation in the average response times of relative humidity transmitters, with the fastest average response time being 7 seconds and slowest average response time being 96 seconds. Further, the test results show that capac-itive-type transmitters had faster response times compared to resistive-type transmitters.
机译:本文报告了在建筑HVAC中使用的六个不同的安装在管道上的相对湿度变送器的响应时间。在六个发送器中,三个是电容性的,其余三个是电阻性的。本文介绍了用于确定相对湿度变送器响应时间的测试硬件,以及对测试条件和实验测试程序的详细说明。实验测试结果表明,相对湿度变送器的平均响应时间存在明显差异,最快的平均响应时间为7秒,最慢的平均响应时间为96秒。此外,测试结果表明,与电阻型变送器相比,电容型变送器具有更快的响应时间。