首页> 外文期刊>ASHRAE Transactions >Energy Analysis of Cleanrooms in an Academic Research Building
【24h】

Energy Analysis of Cleanrooms in an Academic Research Building

机译:学术研究大楼洁净室的能源分析

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The purpose of this study is to perform energy analyses and simulations of a high-technology, academic research building on the University of Maryland (UMD) Campus. The focus of this paper is on facility benchmarking, energy model calibration, and energy efficiency measures (EEMs) proposed and simulated to estimate achievable energy savings for the building's energy-intensive cleanrooms. The high energy intensity of the building, measured as 419 kBtu/ft~2·yr (1322 kWh/m~2·yr), is largely due to the building's cleanrooms, which are responsible for approximately 50% of the total energy consumption in the building. Three EEMs are identified to reduce cleanroom energy consumption by an estimated 21.6% (10.6% of total building energy use). The proposed work contributes significantly to the limited number of cleanroom energy studies published in the academic research community, especially for those cleanrooms embedded in larger buildings.
机译:这项研究的目的是在马里兰大学(UMD)校园内对高科技学术研究大楼进行能源分析和模拟。本文的重点是提出和模拟的设施基准,能源模型校准以及能效措施(EEM),以估算建筑物的高能耗洁净室可实现的节能量。建筑物的高能源强度为419 kBtu / ft〜2·yr(1322 kWh / m〜2·yr),主要归因于建筑物的洁净室,该洁净室约占建筑物总能耗的50%。建筑物。确定了三个EEM,可将无尘室能耗降低约21.6%(占建筑能耗的10.6%)。拟议的工作极大地促进了学术研究界发布的有限的洁净室能源研究,特别是对于那些嵌入大型建筑物的洁净室。

著录项

  • 来源
    《ASHRAE Transactions》 |2015年第2期|71-83|共13页
  • 作者单位

    Department of Mechanical Engineering, University of Maryland, College Park, MD;

    Department of Mechanical Engineering, University of Maryland, College Park, MD;

    Department of Mechanical Engineering, Youngstown State University, Youngstown, Ohio;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng