Performance of Variable-air-volume Air-conditioning System under Reduced Static Pressure Control in an Occupied Office

机译:占用办公室中减少静压控制的可变风量空调系统的性能

获取原文
获取原文并翻译 | 示例
       

摘要

Traditional control of variable air volume (VAV) air conditioning system in office building keeps static pressure in main air duct at constant pressure. This provides excessive static pressure during partial load, resulting in energy wastage. In this study, retrofit control algorithm is adopted to minimize static pressure in main air ducts by varying the static pressure set point. Though static pressure optimization studies were performed in the past, the control methods were implemented to the VAV system either in unoccupied office or by simulation. This paper describes a year round field study that applied a reduced static pressure algorithm to an occupied office floor. Thermal comfort and indoor air quality were evaluated. The results revealed that 8-9% annual energy saving is achievable without sacrificing thermal comfort and indoor air quality.
机译:传统的办公楼可变风量(VAV)空调系统控制将主风管中的静压保持在恒定压力下。这会在部分负载期间提供过大的静压力,从而导致能量浪费。在这项研究中,采用了改造控制算法,通过改变静压设定点来最大程度地减小主风管中的静压。尽管过去进行过静压优化研究,但控制方法已在无人值守的办公室或通过仿真应用于VAV系统。本文描述了一项全年的现场研究,该研究将降低的静压算法应用于占用的办公地板。评价了热舒适性和室内空气质量。结果表明,在不牺牲热舒适性和室内空气质量的前提下,每年可节省8-9%的能源。