首页> 外文期刊>Arabian Journal for Science and Engineering. Section A, Sciences >Optimal Application of Fault Current Limiters for Assuring Overcurrent Relays Coordination with Distributed Generations
【24h】

Optimal Application of Fault Current Limiters for Assuring Overcurrent Relays Coordination with Distributed Generations

机译:用于确保过流继电器与分布代元协调的最佳应用

获取原文
获取原文并翻译 | 示例
       

摘要

This paper addresses the problem of overcurrent relays (OCRs) coordination in presence of DGs. OCRs are optimally set towork in a coordinated manner to isolate faults with minimal impacts on customers. Penetration of DGs into the power system changes the fault current levels seen by the OCRs. This can deteriorate the coordinated operation of OCRs. Operation time difference between backup and main relays can be below the standard limit or even the backup OCR can incorrectly work before the main OCR. Though resetting of OCRs is tedious especially in large systems, it cannot alone restore the original coordinated operation in the presence of DGs. The paper investigates the optimal utilization of fault current limiters (FCLs) to maintain the directional OCR-coordinated operation without any need to OCRs resetting irrespective of DGs status. It is required to maintain theOCRscoordination at minimum cost of prospective FCLs. Hence, the FCL location and sizing problem are formulated as a constrained multi-objective optimization problem. Multi-objective particle swarm optimization is adopted for solving the optimization problem to determine the optimal locations and sizes of FCLs. The proposed algorithm is applied to meshed and radial power systems at different DGs arrangements using different types of FCLs. Moreover, theOCRcoordination problem is studied when the system includes both directional and non-directional OCRs. Comparative analysis of results is provided.
机译:本文解决了DGS存在的过流继电器(OCRS)协调的问题。 OCR是以协调的方式最佳设置毛巾,以隔离对客户影响最小的故障。 DGS进入电力系统的渗透改变了OCRS看到的故障电流水平。这可以恶化OCR的协调操作。备份和主继电器之间的操作时间差可以低于标准限制,甚至备份OCR可能在主OCR之前错误地工作。虽然重置OCRS乏味尤其是在大型系统中,但它不能单独恢复DGS存在下的原始协调操作。本文调查了故障电流限制器(FCLS)的最佳利用,以维持定向OCR协调操作,而无需OCRS重置而无论DGS状态如何重置。需要以最低潜在的FCLS成本维持外科央行。因此,FCL位置和大小写问题被制定为约束的多目标优化问题。采用多目标粒子群优化来解决优化问题以确定FCLS的最佳位置和大小。该算法应用于使用不同类型的FCLS的不同DGS布置的网状和径向电力系统。此外,当系统包括定向和非定向OCRS时,研究了该曲调问题。提供了结果的比较分析。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号