Fire Resistance Test of a Reinforced Concrete Beam-Supporting Column Transfer Structure Joint Unit

机译:钢筋混凝土梁支撑柱转移结构联合单元的耐火试验

获取原文
获取原文并翻译 | 示例
       

摘要

According to the characteristics of a reinforced concrete beam-supporting column transfer structure, two types of beam-supporting column joint unit specimens are designed, and fire resistance tests are conducted on the specimens. Adopting the ISO 834 international standard heating curve for temperature control, the temperatures at the measuring points on the concrete and rebar inside each joint unit specimen and the vertical deformation at the feature position of each joint unit specimen are recorded, the corresponding curves are drawn, and the fire resistance rating is obtained. After the specimens are naturally cooled, the damage to the specimens after reaching the fire resistance rating is observed. The experimental results show the following attributes: After the reinforced concrete beam-supporting column transfer structure joint unit specimen reaches the fire resistance rating, the bending deformation of the transfer girder becomes more concentrated; the damage modes of the beam sections are bending failure; the cracks are largely located approximately 400-500 mm from the maximum bending moment section; and the longitudinal rebar in the crack section of the transfer girder could break under high temperatures. Under the coupling of fire with a constant load, the distribution of internal forces along the axis of the transfer girder changes, causing the girder to deform differently on the two sides of the supported column. Therefore, the influence of a change in the internal force distribution on the fire behavior due to the arrangement of the supported column must be considered.
机译:根据钢筋混凝土梁支撑柱转移结构的特点,设计了两种类型的梁支撑柱关节单元样本,并在样品上进行耐火试验。采用ISO 834国际标准加热曲线进行温度控制,记录每个接合单元样本中混凝土和钢筋上的测量点的温度,并记录每个接合单元样本的特征位置处的垂直变形,相应的曲线被绘制,获得耐火性等级。在自然冷却试样后,观察到达到耐火等级后对样本的损坏。实验结果表明以下属性:在钢筋混凝土梁支撑柱转移结构接合单元试样达到耐火等级之后,转移梁的弯曲变形变得更加浓缩;光束部分的损坏模式是弯曲故障;裂缝距离最大弯矩部分大约400-500毫米;转移梁的裂缝部分中的纵向钢筋可能会在高温下破裂。在恒定负荷的火的耦合下,沿着传递梁的轴线的内部力分布改变,使得梁在支撑柱的两侧不同地变形。因此,必须考虑由于支撑柱的布置而导致的导力分布变化的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号