An analysis of unsymmetrical faults for a 110 kV sub-grid coupling with a superconducting fault current limiter is conducted in this contribution. For the design of the super-conducting fault current limiters it is essential to identify the highest possible voltage during the limitation process. As reference the symmetric three phase fault which generally leads to the highest short-circuit currents is used. Unsymmetrical faults like single line-to-ground fault, line-to-line fault and double line-to-ground fault are investigated in dependence of the superconducting fault current limiter impedance. The analysis shows that the double line-to-ground fault leads to the highest voltage drop during the limitation in the relevant range of impedance. Consequently, this fault is a crucial factor for the design of the superconducting fault current limiter.
机译:在此贡献中,对具有超导故障限流器的110 kV子电网耦合的非对称故障进行了分析。对于超导故障电流限制器的设计,必须在限制过程中确定可能的最高电压。作为参考,使用对称的三相故障,该故障通常会导致最大的短路电流。根据超导故障限流器的阻抗,研究了非对称故障,例如单线接地故障,线间故障和双线接地故障。分析表明,在相关阻抗范围内的限制期间,双线接地故障导致最高的电压降。因此,该故障是超导故障限流器设计的关键因素。