Fault Current Test of a Bifilar Bi-2212 Bulk Coil

机译:双壁Bi-2212散装线圈的故障电流测试

获取原文
获取原文并翻译 | 示例

摘要

A bifilar Bi-2212 bulk coil with parallel shunt resistor was tested under fault current condition using a 3 MVA single-phase transformer in a 220 V–60 Hz line achieving fault current peak of 8 kA. The fault current tests are performed from steady state peak current of 200 A by applying controlled short circuits up to 8 kA varying the time period from one to six cycles. The test results show the function of the shunt resistor providing homogeneous quench behavior of the HTS coil besides its intrinsic stabilizing role. The limiting current ratio achieves a factor 4.2 during 5 cycles without any degradation.
机译:在故障电流条件下,使用3 MVA单相变压器在220 V–60 Hz线路中测试了具有并联分流电阻的Bifilar Bi-2212大容量线圈,故障峰值电流为8 kA。故障电流测试是从200 A的稳态峰值电流通过施加高达8 kA的受控短路(从1到6个周期的时间周期)进行的。测试结果表明,分流电阻器的功能除了具有固有的稳定作用外,还可以为HTS线圈提供均质的淬灭性能。极限电流比在5个周期内达到4.2倍,而没有任何下降。