Current Margin of 275 KV Class HTS Power Cable With Joint Against Fault Current

机译:275 KV级高温超导电力电缆的抗接限电流

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The current margin of a jointed model cable of the 275 kV class high-temperature superconductor (HTS) power cable was measured under fault condition. The cable-to-cable joint is necessary to connect long continuous sections of the power cable. At the joint the superconductor is prone to degradation due to an excessive temperature rise caused by the current passing through normal conducting zones of the joint. The jointed, and for the comparison the joint-less cables were subjected to a short-circuited fault current of 63 kA rms for 0.6 s. In the results, the allowable current margins were about the same for both model cables. The jointed cable degraded at the joint area from the result of the magneto-optical (MO) image. The numerical simulations were performed to clarify current distribution and temperature rise at the cable joint area. The temperature rise as a function of the joint gap was also calculated. The experimental and simulation results were showed in this paper.
机译:在故障条件下测量了275 kV级高温超导体(HTS)电力电缆的模型连接电缆的电流裕度。电缆对电缆的连接对于连接电源线的长连续部分是必需的。在接头处,由于电流流过接头的正常导电区而导致过度的温度升高,超导体易于退化。接头(为比较起见,无接头电缆)经受了63 kA rms的短路故障电流0.6 s。结果,两条模型电缆的允许电流裕量大致相同。由于磁光(MO)图像的结果,接头电缆在接头区域处退化。进行了数值模拟,以弄清电缆接头区域的电流分布和温度升高。还计算了作为接头间隙的函数的温度升高。实验结果和仿真结果表明。