When frost forms and accumulates over the outdoor coil's surface in an air source heat pump (ASHP) unit, system operating performance will be dramatically deteriorated. Reverse cycle defrosting is the most widely used standard defrosting method. A previous related study reported that downwards flowing of melted frost due to gravity over a vertical multi-circuit outdoor coil would decrease the reverse cycle defrosting performance. If the outdoor coil can be changed to horizontally installed, the flow path of melted frost over coil surface can be shortened, and the flow directions of refrigerant and melted frost changed from opposite to orthogonal. Consequently, a better defrosting performance is expected. In this paper, therefore, an experimental study on defrosting performance for an ASHP unit with a horizontally installed multi-circuit outdoor coil was conducted. Experimental results show that, when a vertical outdoor coil was changed to horizontally installed, the defrosting efficiency increased 9.8%, however, with the same defrosting duration at 186 s. Furthermore, when the outdoor air fan was reversed to blowing the melted frost during defrosting, the total mass of the retained water collected decreased 222 g. However, the defrosting efficiency was not increased, but decreased 6.6% because of the heat transfer enhanced between hot coil and cold ambient air. (C) 2015 Elsevier Ltd. All rights reserved.
机译:当霜在空气源热泵(ASHP)单元中形成并积聚在室外盘管的表面时,系统的运行性能将大大降低。逆循环除霜是使用最广泛的标准除霜方法。先前的相关研究报告称,由于重力作用,融化的霜向下流到垂直多回路室外盘管上会降低反向循环除霜性能。如果能够将室外盘管改变为水平安装,则可以缩短在盘管表面上的融霜的流动路径,并且制冷剂和融霜的流动方向从相反方向变为正交。因此,期望更好的除霜性能。因此,本文对水平安装多回路室外盘管的ASHP机组除霜性能进行了实验研究。实验结果表明,将垂直室外盘管改为水平安装时,除霜效率提高了9.8%,而相同的除霜时间为186 s。另外,在除霜时使室外风扇反转为吹融化的霜时,收集的滞留水的总质量减少了222g。但是,除霜效率没有提高,而是下降了6.6%,这是因为在热盘管和冷空气之间的传热增强了。 (C)2015 Elsevier Ltd.保留所有权利。

著录项

  • 来源
    《Applied Energy》 |2016年第1期|371-382|共12页
  • 作者单位

    Guangdong Univ Technol, Sch Mat & Energy, Guangdong Prov Key Lab Funct Soft Condensed Matte, Guangzhou, Guangdong, Peoples R China|Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China;

    Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China;

    China Univ Petr East China, Coll Pipeline & Civil Engn, Qingdao, Shandong, Peoples R China;

    Univ Pretoria, Dept Elect Elect & Comp Engn, ZA-0002 Pretoria, South Africa;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Air source heat pump; Defrosting; Experiment; Multi-circuit; Horizontally installed;

    机译:空气源热泵;除霜;实验;多回路;水平安装;

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号