首页> 外文期刊>Annals of nuclear energy >Calibration method of liquid zone controller using the ex-core detector signal of CANDU 6 reactor
【24h】

Calibration method of liquid zone controller using the ex-core detector signal of CANDU 6 reactor

机译:利用CANDU 6反应堆核外检测器信号校准液域控制器的方法

获取原文
获取原文并翻译 | 示例
           

摘要

The Phase-B test (low-power reactor physics test) is one of the commissioning tests for Canada Deuterium Uranium (CANDU) reactors that ensures the safe and reliable operation of the core during the design lifetime. The Phase-B test, which includes the approach to the first criticality at low reactor powers, is performed to verify the feasibility of the reactor's physics design and to ensure the integrity of the control and protection facilities. The commissioning testing of pressurized heavy water moderated reactors (PHWRs) is usually performed only once (at the initial commissioning after construction). The large-scale facilities of the Wolsong nuclear power plant (NPP) Unit 1 have been gradually improved since May 2009 to extend its lifetime. The refurbishment was completed in April 2011 - then this NPP has been in operation again. We discusses the new methodology and measurement system that uses an ex-core detector signal for liquid zone controller (LZC) calibration of the Phase-B test instead of conventional methods. The inverse kinetic equation in the reactivity calculator is modified to treat the 17 delayed neutron groups including 11 photo-neutron fractions. The signal acquisition resolution of the reactivity calculator was enhanced and installed reactivity calculating module by each channel. The ex-core detector was confirmed to be applicable to a large reactor core, such as the CANDU 6 by comparison with the in-core flux detector signal. A preliminary test was performed in Wolsong NPP Unit 2 to verify the robustness of the reactivity calculator. This test convincingly demonstrated that the reactivity calculator works well. Commissioning testing of Wolsong NPP Unit lwas performed after successful refurbishment in June 2011. The LZC calibration test was completed successfully, and the requirement of the test was satisfied. The test difference was biased by approximately -6% between 20% and 70% of the liquid zone level. Moreover, the test was completed within 4 h compared with about 48 h required for Wolsong NPP Units 2, 3, and 4.
机译:B相测试(低功率反应堆物理测试)是加拿大氘铀(CANDU)反应堆的调试测试之一,可确保堆芯在设计寿命期间安全可靠地运行。 B级测试包括在低反应堆功率下达到第一个临界点的方法,旨在验证反应堆物理设计的可行性并确保控制和保护设施的完整性。加压重水缓和堆(PHWR)的调试测试通常仅执行一次(在建造后的初始调试中)。自2009年5月以来,伍尔松核电站(NPP)1号机组的大型设施已逐步改善,以延长其使用寿命。翻新工程于2011年4月完成-然后,该NPP再次投入运行。我们讨论了一种新的方法和测量系统,该系统使用核外检测器信号进行B相测试的液体区域控制器(LZC)校准,而不是使用传统方法。修改了反应性计算器中的逆动力学方程,以处理包括11个光中子分数的17个延迟中子基团。每个通道增强了反应性计算器的信号采集分辨率并安装了反应性计算模块。通过与堆芯内磁通检测器信号进行比较,证实了堆芯前检测器适用于大型反应堆堆芯,例如CANDU 6。在Wolsong NPP 2号机组中进行了初步测试,以验证反应性计算器的耐用性。该测试令人信服地证明了反应性计算器运行良好。于2011年6月成功翻新后,对伍尔松核电厂1号机组进行了调试测试。LZC校准测试已成功完成,并且满足测试要求。在液体区域液位的20%和70%之间,测试差异有大约-6%的偏差。此外,测试在4小时内完成,而Wolsong NPP 2号,3号和4号机组则需要约48小时。

著录项

  • 来源
    《Annals of nuclear energy》 |2013年第4期|209-217|共9页
  • 作者单位

    Korea Hydro & Nuclear Power Central Research Institute, 1312-70, Yusungdaero, Yusung-Gu, Daejeon 305 343, Republic of Korea;

    Korea Hydro & Nuclear Power Central Research Institute, 1312-70, Yusungdaero, Yusung-Gu, Daejeon 305 343, Republic of Korea;

    Korea Hydro & Nuclear Power Central Research Institute, 1312-70, Yusungdaero, Yusung-Gu, Daejeon 305 343, Republic of Korea;

    Korea Hydro & Nuclear Power Central Research Institute, 1312-70, Yusungdaero, Yusung-Gu, Daejeon 305 343, Republic of Korea;

    Yeungnam University, 280 Daehak-Ro, Cyeongsan, Gyeongbuk 712 749, Republic of Korea;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    candu 6; phase-b; liquid zone control system; reactivity calculator;

    机译:candu 6;b相;液区控制系统;反应性计算器;