首页> 外文期刊>American Water Works Association Journal >Integration Of Desalinated Seawater Into A Distribution System: a Corrosion Pilot Study
【24h】

Integration Of Desalinated Seawater Into A Distribution System: a Corrosion Pilot Study

机译:将淡化海水整合到配电系统中:腐蚀试验研究

获取原文
获取原文并翻译 | 示例
           

摘要

A proposed seawater desalination plant for Carlsbad, Calif., will produce treated water that varies from the city's typical imported surface water supply. A six-month pilot study was conducted to compare how Carlsbad distribution materials would be affected by the potential corrosion that might arise from conditioned desalinated seawater versus the city's typical supply. Various distribution and home plumbing appurtenances were evaluated in parallel test systems, including copper pipe, brass service meters, cement-mortar-lined pipe, and cast-iron distribution system gate valves. Corrosion was assessed by analyzing changes in water quality caused by pipe corrosion or passivation, including metal concentration (iron, zinc, lead, copper, and aluminum), calcium, alkalinity, and turbidity changes. Pilot testing demonstrated that conditioned reverse osmosis permeate achieving minimum water quality goals-alkalinity of 45 mg/L as calcium carbonate (CaCO_3), hardness of 40 mg/L as CaCO_3, and pH of 8.5-was not likely to trigger new corrosion problems in the Carlsbad distribution system.
机译:加利福尼亚州卡尔斯巴德市拟建的海水淡化厂将生产与城市典型的进口地表水量不同的经处理水。进行了为期六个月的试点研究,以比较卡尔斯巴德配电材料将如何受到条件化淡化海水与城市典型供水所产生的潜在腐蚀的影响。在并行测试系统中评估了各种分配和家庭水暖配件,包括铜管,黄铜维修仪表,水泥砂浆衬里管道和铸铁分配系统闸阀。通过分析由管道腐蚀或钝化引起的水质变化来评估腐蚀,包括金属浓度(铁,锌,铅,铜和铝),钙,碱度和浊度变化。试点测试表明,经过调节的反渗透可以达到最低水质目标-碳酸钙(CaCO_3)的碱度为45 mg / L,碳酸钙(CaCO_3)的碱度为40 mg / L,pH 8.5-不太可能引发新的腐蚀问题。卡尔斯巴德(Carlsbad)发行系统。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号