Estimation of bias with the single-zone assumption in measurement of residential air exchange using the perfluorocarbon tracer gas method

机译:使用全氟化碳示踪气体法测量住宅空气交换时的单区假设偏差估计

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Residential air exchange rates (AERs) are vital in understanding the temporal and spatial drivers of indoor air quality (IAQ). Several methods to quantify AERs have been used in IAQ research, often with the assumption that the home is a single, well-mixed air zone. Since 2005, Health Canada has conducted IAQ studies across Canada in which AERs were measured using the perfluorocarbon tracer (PFT) gas method. Emitters and detectors of a single PFT gas were placed on the main floor to estimate a single-zone AER (AER1z). In three of these studies, a second set of emitters and detectors were deployed in the basement or second floor in approximately 10% of homes for a two-zone AER estimate (AER2z). In total, 287 daily pairs of AER2z and AER1z estimates were made from 35 homes across three cities. In 87% of the cases, AER2z was higher than AER1z. Overall, the AER1z estimates underestimated AER2z by approximately 16% (IQR: 5–32%). This underestimate occurred in all cities and seasons and varied in magnitude seasonally, between homes, and daily, indicating that when measuring residential air exchange using a single PFT gas, the assumption of a single well-mixed air zone very likely results in an under prediction of the AER.
机译:住宅空气交换率(AER)对于了解室内空气质量(IAQ)的时空驱动因素至关重要。 IAQ研究中使用了几种量化AER的方法,通常是假设房屋是一个单一的,空气充分混合的区域。自2005年以来,加拿大卫生部在加拿大进行了IAQ研究,其中使用全氟化碳示踪剂(PFT)气体方法测量了AER。单一PFT气体的发射器和检测器放在主地板上,以估计单区域AER(AER1z)。在其中的三项研究中,在地下室或二楼的大约10%的房屋中部署了第二组发射器和检测器,以进行两区AER估算(AER2z)。总共从三个城市的35个家庭中进行了287对每日的AER2z和AER1z评估。在87%的情况下,AER2z高于AER1z。总体而言,AER1z估计低估了AER2z约16%(IQR:5-32%)。这种低估发生在所有城市和季节,并且在季节之间,在房屋之间和每天之间变化幅度很大,这表明,当使用单一的PFT气体测量住宅的空气交换量时,假设单一的混合空气区域很可能导致预测不足。 AER。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号